Rated voltage and blocking capacity | 250V AC–100kA 250V DC (L/R = 10ms)–100kA |
---|---|
Minimum block-off current | 250V AC/DC – 5 times the rated amperage |
Maximum arc voltage | 550V |
Rated voltage and blocking capacity | 250/350V AC–100kA 400V DC (L/R = 2ms)–10kA |
---|---|
Minimum block-off current | 350V AC/400V DC – 5 times the rated amperage |
Maximum arc voltage | 700V 800V |
※Read “PROTECT FUSE USER’S GUIDE” and “FOR SAFE USE” at the back of this catalog before use.
※When purchasing a product with an Alarm indicating Fuse, enter “S” immediately after the ampere rating in the product name (e.g. 350GH-200S).
※The minimum working voltage of the alarm fuse is 10 V.
When applying the standard to UL standard approved items, use the fuse in the following rating.
Rated voltage and blocking capacity | 250V AC–100kA 250V DC (L/R = 10ms)–100kA |
---|
Rated voltage and blocking capacity | 380V AC–10kA 400V DC (L/R = 2ms)–10kA |
---|
When applying the standard to CCC standard approved items, use the fuse in the following rating.
Rated voltage and blocking capacity | 350V AC–50kA 250V DC (L/R = 10ms)–50kA |
---|
Voltage | Electric Current | Cylinder Size(Estimated) |
---|---|---|
250V / 350V | 16~800A | φ17×25~ |
Installation Method | RoHS Order | Standard Approved |
Screwed | ◯ |